Cable Types & Ratings
Cable construction and electrical ratings
Choose the right cable type for the application
European and North American cables use different names and conductor sizes. The cable code gives useful information, but it does not give the full rating of a finished power cord.
Quick rule The complete cord is limited by its lowest-rated part: mains plug, IEC plug, connector, cable, conductor size, terminals or approval.
How to read a European cable code
European harmonised cable names follow a simple system. This example shows the main parts of H05VV-F 3G1.0 mm².
G means that the cable includes a green/yellow protective-earth conductor. X means that it does not.
Common European cable types
These cable types are common in European power cords. All four types below are normally marked 300/500 V. Temperature values can vary with the exact standard, material compound, manufacturer and movement conditions.
| Cable type | Construction | Temperature guide | Typical use | Important point |
|---|---|---|---|---|
|
H05VV-FSTANDARD PVC
|
PVC core insulation and PVC outer sheath | Usually up to 70 °C at the conductor* | Standard indoor IT, office and appliance connections | Not intended for direct contact with hot parts or permanent outdoor use |
|
H05V2V2-FHEAT-RESISTANT PVC
|
Heat-resistant PVC core insulation and outer sheath | Up to 90 °C at the conductor* | Warm indoor areas and many C15 high-temperature cords | Higher temperature rating than H05RR-F, but not a 120 °C cable |
|
H05RR-FRUBBER
|
Rubber core insulation and rubber outer sheath | Often -25 to +60 °C in flexible use* | Flexible connections, damp areas and light mechanical stress | Choose it for rubber construction and flexibility, not for a higher heat rating |
|
H05Z1Z1-FLSZH
|
Low-smoke, halogen-free core insulation and outer sheath | Product-specific; often 60–70 °C service maximum* | Projects that specify low-smoke, halogen-free materials | LSZH does not mean fire-resistant or circuit-integrity cable |
The drawings show a basic three-core construction only. They are not to scale, and actual jacket colours can be different.
*These values are a selection guide, not a product certificate. Always check the specification of the exact cable and finished cord.
Conductor size and current
A larger conductor can carry more current, but conductor size alone does not set the rating of a finished cord.
| Metric marking | Meaning | Common MK Cable use | What to check |
|---|---|---|---|
| 3G0.75 mm² | Three cores including earth; each conductor is 0.75 mm² | Many standard C14 to C13 cords | Exact cord rating, length, connectors and approval |
| 3G1.0 mm² | Three cores including earth; each conductor is 1.0 mm² | C14 to C13, C14 to C15 and selected locking cords | A 1.0 mm² cable does not automatically change a 10 A connector limit |
| 3G1.5 mm² | Three cores including earth; each conductor is 1.5 mm² | Many 16 A C20 to C19 cords | The complete cord must still be rated and approved for 16 A |
North American cords use different cable names and AWG sizes. The next section explains the main differences.
North American cable types and AWG
North American flexible cords use UL and CSA cable names. SJT is common in data-centre, IT and industrial power cords.
Example: SJTOW 3 x 14 AWG is a three-conductor, 14 AWG, 300 V flexible cord with thermoplastic materials, an oil-resistant outer jacket and a weather-resistant rating. Always check the full cable print and approval.
| Cable type | Basic meaning | Typical use | Important point |
|---|---|---|---|
| SJT | 300 V junior-service cord with thermoplastic insulation and jacket | Indoor IT, data-centre, appliance and industrial cordsets | Standard SJT does not add an outdoor or oil-resistant rating |
| SJTW | SJT construction with a weather-resistant rating | Indoor or outdoor cords where the exact product is approved for the environment | Check the wet-location, temperature and sunlight markings |
| SJTOW | SJT with an oil-resistant outer jacket and weather resistance | More demanding industrial and outdoor applications | The exact oil and environmental rating must be confirmed |
| SVT | Lighter thermoplastic flexible cord, normally 300 V | Smaller appliances, office equipment and many 18 AWG cordsets | SVT is not the same mechanical-use class as SJT |
AWG and mm² are different systems
AWG numbers work in reverse: a lower AWG number means a larger conductor. The mm² values below show nominal copper area only. They are not direct product equivalents.
| AWG size | Nominal area | Example SJT cable ampacity* | Common finished-cord limit |
|---|---|---|---|
| 18 AWG | About 0.823 mm² | 10 A | Often 10 A, depending on both ends and approval |
| 16 AWG | About 1.31 mm² | 13 A | Often up to 13 A with suitable components |
| 14 AWG | About 2.08 mm² | 18 A | Commonly 15 A when the plug or connector is the limit |
| 12 AWG | About 3.31 mm² | 25 A | Commonly 20 A when the plug or connector is the limit |
*These are common ampacity examples for listed three-conductor North American flexible cable. They are not automatic cordset ratings. Temperature, length, plug, IEC connector and the approval of the finished cord can reduce the allowed current.
SJT compared with harmonised cable
SJT and H05VV-F can look similar and can be used for similar products. They are not direct equivalents.
| Point | North American system | European harmonised system |
|---|---|---|
| Common types | SJT, SJTW, SJTOW, SVT | H05VV-F, H05V2V2-F, H05RR-F, H05Z1Z1-F |
| Main cable standards | UL 62 and CSA C22.2 No. 49 | EN 50525 and related national approvals |
| Size marking | AWG; lower number means larger wire | mm²; larger number means larger conductor area |
| Voltage class | SJT and SVT are normally 300 V cable types | H05 types are normally marked 300/500 V |
| Finished-cord approval | UL/cUL or CSA approval for the exact cord | Required plug, cable and cordset approvals for the destination country |
| Can one replace the other? | Only when the finished cord has the required North American approval | Only when the finished cord has the required European or national approval |
Why current ratings can be different
The same IEC connector shape can have a different finished-cord rating under a different approval system. These examples show common MK Cable configurations.
| Cord example | Cable | Typical finished-cord rating | Main reason for the limit |
|---|---|---|---|
| C14 to C13 | H05VV-F 3G0.75 or 3G1.0 mm² | Up to 10 A / 250 V | Harmonised cordset and IEC connector rating |
| C14 to C13 | 18/3 SJT | Commonly 10 A / 250 V | 18 AWG conductors or another cord component |
| C14 to C13 | 14/3 SJT | Up to 15 A / 250 V with the correct UL/cUL approval | Approved plug and connector rating |
| NEMA 5-15 to C13 | 18/3 SJT or SVT | Commonly 10 A / 125 V | 18 AWG conductors or connector rating |
| NEMA 5-15 to C19 | 14/3 SJT | Up to 15 A / 125 V | NEMA 5-15 plug |
| C20 to C19 | H05VV-F 3G1.5 mm² | Up to 16 A / 250 V | Harmonised IEC connector rating |
| C20 to C21 | 12/3 SJT | Up to 20 A / 250 V with the correct UL/cUL approval | Approved C20/C21 components |
These are practical examples, not a universal rating table. Always use the current and voltage printed on the exact finished cord and shown in its approval documents.
Choose by application
H05VV-F
A common choice for standard indoor power connections where there is no special heat, rubber or LSZH requirement.
H05V2V2-F
Use when the equipment and working conditions require a higher cable temperature rating than standard PVC or H05RR-F.
H05RR-F
Use when the specification asks for rubber or when flexibility, damp conditions and light mechanical stress are important.
H05Z1Z1-F
Use when the project specification requires low-smoke, halogen-free materials for the power cord.
SJT and SVT
Use a North American cable type when the project needs UL/cUL or CSA-approved cord construction and AWG conductor sizes.
Five checks before ordering
Check both ends
Identify the power-source outlet and the inlet on the equipment.
Open the IEC connector guideCheck current and voltage
Use the rating of the exact finished cord, not only the cable or connector value.
Check heat and materials
Confirm temperature, indoor or outdoor use, moisture and mechanical stress.
Check size and length
Longer cords and higher loads may need a larger conductor. Check the exact specification.
Check approvals
Confirm the approval and product documents required for the destination country.
Cable questions
Is H05V2V2-F more heat-resistant than H05RR-F?
Does a C15 connector make the complete cord suitable for 120 °C?
Does 3G1.5 mm² always mean 16 A?
Is LSZH cable fire-resistant?
Can H05VV-F be used outdoors?
What does 3G1.0 mm² mean?
What does SJT mean?
Is 18 AWG the same as 0.75 mm²?
Why can one C14 to C13 cord be 10 A and another 15 A?
Can SJT replace H05VV-F?
Need help choosing the cable type?
Send us the plug and connector, current, voltage, temperature, environment, length, colour, quantity and destination country.